Engineering Calculators / Current Capacity
Current Capacity Calculator
Look up the allowable ampacity of a copper conductor by AWG size and insulation temperature rating. Reference values follow NEC Table 310.16.
Result
Select a wire size and insulation rating.
Reference table — copper conductors (A)
| AWG | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| 14 | 15 | 20 | 25 |
| 12 | 20 | 25 | 30 |
| 10 | 30 | 35 | 40 |
| 8 | 40 | 50 | 55 |
| 6 | 55 | 65 | 75 |
| 4 | 70 | 85 | 95 |
| 3 | 85 | 100 | 115 |
| 2 | 95 | 115 | 130 |
| 1 | 110 | 130 | 145 |
| 1/0 | 125 | 150 | 165 |
| 2/0 | 145 | 175 | 195 |
| 3/0 | 165 | 200 | 225 |
| 4/0 | 195 | 230 | 260 |
Corrections to apply
- Ambient temperature above 30 °C requires a correction factor from the NEC tables.
- More than three current-carrying conductors bundled together requires a bundling adjustment.
- The lowest temperature rating in the circuit governs — a 90 °C wire on a 75 °C-rated terminal must use the 75 °C value.
- For harnesses, also verify the connector and terminal current ratings.
Values are uncorrected reference values from NEC Table 310.16. Verify against the current NEC edition and your project specifications before use.