Engineering Calculators / Wire Gauge
Wire Gauge Calculator
Enter the load and cable run to get a suggested AWG size. The recommendation is based on the voltage-drop limit for copper conductors; the NEC ampacity check is shown separately as a reference.
Result
Inputs changed — recalculateEnter your values and press Calculate.
How it works
The recommendation works in two layers. First, voltage-drop sizing: the calculator finds the smallest listed AWG copper conductor whose cross-section keeps the loop voltage drop within your limit. Sizes from 4/0 AWG down to 28 AWG are all candidates — 16 AWG and finer are common in custom harnesses even though they have no NEC building-wire ampacity rating.
Second, ampacity review: the recommended size is checked against NEC Table 310.16 (copper, 75 °C column). This is a building-wire reference, not a harness rating — it is shown as context and never used to exclude a size. When the pick has no NEC entry or its listed rating is below the load, the result is flagged as “ampacity not verified”, and where one exists a NEC-listed alternative is shown for building-wire use.
Voltage drop is computed as VD = k × I × L × ρ / A, where k = 2 for DC and single-phase AC (out-and-back loop), k = √3 for three-phase AC, ρ = 0.01724 Ω·mm²/m (copper at 20 °C), L is the one-way length in meters, and A is the conductor cross-section in mm².
Three-phase results assume a balanced load and use the line-to-line voltage; power factor and line reactance are ignored (resistive estimate). The resistivity is the 20 °C reference — no temperature correction is applied in this model, so drops at elevated operating temperatures will be somewhat higher.
A one-way length of 0 m is a mathematical edge case (zero resistive drop); real harnesses always include termination and contact resistance not covered here.
Have a Cable Assembly Project in Mind?
Send us your drawings, component references, or project requirements. We can review the available information and help identify the next steps for quotation.