Engineering Calculators / Voltage Drop

Voltage Drop Calculator

Check how much voltage a cable run loses at a given load. Works for DC, single-phase AC, and three-phase AC, with copper or aluminum conductors.

Result

Enter your values and press Calculate.

How it works

For DC and single-phase AC the loop drop is VD = 2 × I × L × ρ / A; for three-phase AC it is VD = √3 × I × L × ρ / A. ρ is the conductor resistivity (ρ = 0.01724 Ω·mm²/m for copper and 0.0282 Ω·mm²/m for aluminum, both at 20 °C), L the one-way length, and A the cross-section.

The calculation is resistive only — it ignores reactance, which is a valid simplification for the low-voltage, short-distance runs typical of wire harnesses. Three-phase results assume a balanced load and use the line-to-line voltage. Conductor resistance rises with temperature, so drops at elevated operating temperatures will be somewhat higher than the 20 °C reference value.

Have a Cable Assembly Project in Mind?

Send us your drawings, component references, or project requirements. We can review the available information and help identify the next steps for quotation.